The 3VA1032-2ED32-0DA0: At 415 V this MCCB interrupts 32 kA, and at 440 V it's still 13.6 kA. Power loss is 13.1 W maximum — modest for a 32 A frame, so adjacent devices in a crowded enclosure won't see excessive heat soak. The TM210 release is fixed thermal-magnetic; no electronic adjustment, but for a straight feeder or non-critical motor branch that's fine.
Footprint is 76.2 mm wide by 130 mm tall by 70 mm deep — standard SENTRON 3VA1 frame size. Bolts onto a backplate or mounts on a DIN rail adapter. The UVR coil takes up a bit of internal space but doesn't change the external dimensions. If you're swapping into a panel cut for a 3VA1, this drops in without re-drilling.