Siemens 3VA1032-2ED32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1032-2ED32-0DC0 MCCB, 32 A, 3-Pole, 52.5

MPN3VA1032-2ED32-0DC0

Siemens SENTRON 3VA1032-2ED32-0DC0, molded case circuit breaker, 3-pole, 32 A rated continuous current Iu, breaking capacity 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, 7.5 kA at 690 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1032-2ED32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-2ED32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1032-2ED32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1032-2ED32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1032-2ED32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED32-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1032-2ED32-0DC0 is a 3-pole molded case circuit breaker (MCCB) rated for 32 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. It's part of the SENTRON 3VA line — the standard panelboard and distribution board breaker for commercial and industrial installations up to 690 V.

Breaking capacity is listed at four voltage points: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The 52.5 kA at 240 V covers single-phase line-to-neutral faults on a 240/415 V wye system. For a 690 V motor feeder, the 7.5 kA rating still handles most industrial fault levels, but verify against your transformer's nameplate.

Current derating and ambient temperature

At 55 °C it drops to 30.72 A, at 60 °C to 30.08 A, at 65 °C to 29.44 A, and at 70 °C to 28.8 A.

The auxiliary contacts let you wire a remote status signal — open/closed indication to a PLC or a panel lamp.

Frequently asked questions

Where can I buy 3VA1032-2ED32-0DC0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1032-2ED32-0DC0 at 415 V?

32 kA at 415 V, which is the figure most panel designers use for a 400 V three-phase system.

Does 3VA1032-2ED32-0DC0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release, plus 2 auxiliary switches (HQ type).