Its 32 A rated continuous current (Iu) holds steady from 40 °C up to 50 °C, then derates to 30.72 A at 55 °C and 28.8 A at 70 °C — so a panel running at 50 °C ambient gets the full 32 A, but above that you lose headroom. The breaking capacity climbs with system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The TM210 overcurrent release provides thermal-magnetic protection — thermal for overloads, magnetic for short-circuits. It does carry a shunt trip (STL) for remote tripping, and a voltage trigger is present. The latching endurance is rated at 15,000 operations, which is typical for a panelboard MCCB seeing occasional switching. Front IP40 protection keeps dust and tools out of the breaker face — fine for a dry indoor panel, but not for washdown environments. The 70 mm depth, 76.2 mm width, and 130 mm height match the standard 3VA frame footprint, so it drops into existing SENTRON panel layouts without re-drilling the gland plate.
The shunt trip (STL) auxiliary release (order code 3VA9688-0BL32) is integrated; no separate auxiliary contact block is needed for remote trip. Verify the control voltage for the shunt trip matches your panel's 24 VDC or 230 VAC supply.