Skip to main content
Siemens 3VA1032-2ED32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-2ED32-0JC0 SENTRON MCCB, 32 A, 3-Pole, 52.5

MPN3VA1032-2ED32-0JC0

Siemens SENTRON 3VA1032-2ED32-0JC0, molded case circuit breaker, 3-pole, 32 A, 52.5 kA at 240 V, TM210 release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-2ED32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-2ED32-0JC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1032-2ED32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1032-2ED32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1032-2ED32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED32-0JC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1032-2ED32-0JC0 is a SENTRON molded case circuit breaker with a TM210 thermal-magnetic overcurrent release, rated for 32 A continuous current at 40 °C and 3-pole switching. Its interrupting capacity hits 52.5 kA at 240 V and 32 kA at 415 V, so it handles high-fault utility feeds or transformer secondaries without cascading upstream.

Above that it steps down: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C.

Built-in auxiliary and shunt trip

The shunt trip is wired separately from the main poles — pull 24 VDC or 230 VAC (per the release rating) to the designated terminals and it opens the breaker on command. No undervoltage release, no ground-fault module, no communication card. If you need remote status or emergency stop integration, the aux switches and shunt trip cover it without adding a separate contactor.

Frequently asked questions

How do I get current pricing and availability for 3VA1032-2ED32-0JC0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

Will 3VA1032-2ED32-0JC0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

Both are 3-pole SENTRON MCCBs with the same 76.2 mm width and 70 mm depth, so the footprint and bus-bar spacing are identical. The 3VA1032 carries a higher interrupting capacity (52.5 kA vs the 3VA1010's lower rating at 240 V) and a TM210 release; the 3VA1010 uses a TM210 as well. No rewiring needed for the line and load connections, but verify the shunt trip wiring if the original used a different release option.

What compliance documentation does this brand provide for 3VA1032-2ED32-0JC0?

Siemens SENTRON MCCBs carry CE marking for the European market and are designed to meet IEC 60947-2. UL and CSA listings are standard for the 3VA series, though specific file numbers should be confirmed from the nameplate or the manufacturer's declaration of conformity.

MPN