Skip to main content
Siemens 3VA1032-2ED36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-2ED36-0AH0 SENTRON MCCB, 32 A, 3-Pole, 52.5

MPN3VA1032-2ED36-0AH0

Siemens SENTRON 3VA1, molded case circuit breaker, 3-pole, 32 A (40 °C), 52.5 kA at 240 V, line protection, TM210 release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-2ED36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10322ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1032-2ED36-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.10.6 W
3VA1032-2ED36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1032-2ED36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1032-2ED36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED36-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1032-2ED36-0AH0 is a SENTRON 3VA1 molded case circuit breaker for line protection, rated 32 A continuous at 40 °C with a TM210 thermal-magnetic release. It interrupts 52.5 kA at 240 V and 32 kA at 415 V, making it a solid pick for a main feeder or large branch in a 400 V panel where you need real fault-clearing headroom without stepping up to a bigger frame.

The 32 A continuous rating holds flat from 40 °C up to 50 °C, then only drops to 30 A by 70 °C — so in a warm enclosure you still get nearly the full nameplate. The 52.5 kA at 240 V and 32 kA at 415 V tell you this breaker can sit upstream of a lot of downstream gear without needing a current-limiting fuse ahead of it; those are real SCCR numbers for a 3-pole frame this size. Dimensions are 76.2 mm wide, 130 mm tall, 70 mm deep — it's a standard 3-pole MCCB footprint for a DIN-rail or screw-mount panel. The 70 mm depth leaves room behind the gland plate for wiring without jamming the enclosure door.

It's not on any published phase-out or last-time-buy notice. For a BOM freeze, this part is stable — no imminent PCN risk.

Frequently asked questions

What is the depth of this MCCB?

The 3VA1032-2ED36-0AH0 has a depth of 70 mm (2.76 in), which fits standard panel depths without crowding the gland plate.

MPN
3VA1032-2ED36-0AH0