Siemens SENTRON 3VA1032-2ED36-0HC0 — 32 A MCCB with TM210 Release
Breaking capacity steps: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That 52.5 kA figure at 240 V gives you headroom on most North American 240/120 V distribution panels; the 32 kA at 415 V covers the common European 400 V three-phase grid. Derating is tight up to 50 °C — the breaker holds its full 32 A rating at 40 °C, 45 °C, and 50 °C. At 55 °C it drops to 30.72 A, at 60 °C to 30.08 A, at 65 °C to 29.44 A, and at 70 °C to 28.8 A. Plan your continuous load accordingly.
Fit and Integration — Panel Space and Wiring
The 3VA1032-2ED36-0HC0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. No surprises if you're swapping in from a 3VA10 or 3VA11 frame. If your safety circuit needs an undervoltage release, this variant doesn't carry one; you'd need a different order code. No communication module or phase-failure detection on this version.