Skip to main content
Siemens 3VA1032-2ED36-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-2ED36-0KC0 SENTRON MCCB, 32 A, 3-Pole, 52.5

MPN3VA1032-2ED36-0KC0

Siemens SENTRON 3VA1032-2ED36-0KC0, molded case circuit breaker, 3-pole, 32 A, line protection, 52.5 kA at 240 V, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-2ED36-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-2ED36-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1032-2ED36-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1032-2ED36-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED36-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1032-2ED36-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED36-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The 52.5 kA interrupting rating at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V tell you the fault current it can safely clear at each voltage — critical for selectivity studies and SCCR compliance upstream of a panel. The rated continuous current Iu of 32 A holds across 40 °C to 50 °C, then derates to 28.8 A at 70 °C; that thermal curve governs the actual load you can hang on it in a warm enclosure. Fit: the breaker occupies 130 mm height, 76.2 mm width, 70 mm depth — standard SENTRON 3VA footprint for a 32 A frame. Two HQ auxiliary switches are factory-fitted (the integrated auxiliary trip is order code 3VA9688-0BL33).

Frequently asked questions

Where can I buy the 3VA1032-2ED36-0KC0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quotation; availability and current pricing are confirmed at quote time.

What are the key interrupting ratings for the 3VA1032-2ED36-0KC0?

At 240 V it interrupts 52.5 kA, at 415 V it interrupts 32 kA, at 440 V it interrupts 13.6 kA, and at 690 V it interrupts 7.5 kA.

What compliance documentation does Siemens provide for this MCCB?

The reference code per DIN EN 81346-2 is Q, and the protection class on the front is IP40. The evidence does not list RoHS, REACH, UL, or IEC certificates directly, but SENTRON 3VA breakers are typically UL 489 and IEC 60947-2 listed; confirm the specific certification package with the order.

MPN
3VA1032-2ED36-0KC0