Skip to main content
Siemens 3VA1032-3ED32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-3ED32-0BC0 SENTRON MCCB, 32 A, 3-Pole, 75.6

MPN3VA1032-3ED32-0BC0

Siemens SENTRON 3VA1032-3ED32-0BC0, molded case circuit breaker, 3-pole, 32 A at 40 °C, breaking capacity 75.6 kA at 240 V, line protection, undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-3ED32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10323ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-3ED32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.13.1 W
3VA1032-3ED32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1032-3ED32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-3ED32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1032-3ED32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-3ED32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1032-3ED32-0BC0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 32 A at 40 °C and a breaking capacity of 75.6 kA at 240 V.

The 75.6 kA at 240 V is the highest interrupting rating on record, dropping to 52.5 kA at 415 V and 32 kA at 440 V.

The breaker holds 32 A from 40 °C up to 50 °C, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C. That flat curve means it runs at full rating in most enclosed panels without needing a larger frame. Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard panel cutouts for a 3-pole MCCB.

Frequently asked questions

What auxiliary options are included on this breaker?

It ships with an undervoltage release (UVR) and two auxiliary switches (HQ design). No communication function or ground-fault monitoring is fitted.

MPN