The 3VA1032-3ED32-0DA0: At 240 V it interrupts 75.6 kA, at 415 V it's 52.5 kA, and at 440 V it drops to 32 kA. That 75.6 kA at 240 V gives you serious fault-current headroom for a 32 A frame — useful if you're feeding a sub-panel with a high-capacity transformer upstream and need selectivity with a downstream 32 A breaker.
Thermal derating and the TM210 trip
The TM210 thermal-magnetic trip holds 32 A from 40 °C up to 50 °C, then derates to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C.
Built-in undervoltage release
That means if your control voltage dips below the dropout threshold, the breaker trips automatically. No need to add a separate shunt trip module or wire an external relay for undervoltage protection. The UVR is factory-integrated, so verify your control voltage matches the release rating before wiring.
No need to re-drill the sub-panel or re-lay bus bars if you're swapping from a different 3VA variant.