The Siemens SENTRON 3VA1032-3ED32-0DC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 32 A at 40 °C to 50 °C, derating to 30 A at 70 °C. The interrupting ratings are 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V — these are the fault currents the breaker can safely clear at each voltage level without welding or rupturing. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. Maximum power loss is 13.1 W, relevant for thermal budgeting in a sealed panel.

Siemens SENTRON 3VA1032-3ED32-0DC0 MCCB, 32 A, 75.6 kA at 24
Siemens SENTRON 3VA1032-3ED32-0DC0, molded case circuit breaker, 3-pole, 32 A, 75.6 kA at 240 V, line protection, with undervoltage release.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA10323ED320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 32 A |
| Current at 45 °C | 32 A |
| Current at 50 °C | 32 A |
| Current at 55 °C | 31 A |
| Current at 60 °C | 31 A |
| Current at 65 °C | 30 A |
| Current at 70 °C | 30 A |
| Switching capacity class | N |
| Breaking capacity at 240 V | 75.6 kA |
| Breaking capacity at 415 V | 52.5 kA |
| Breaking capacity at 440 V | 32 kA |
| Breaking capacity at 500 V | 7.5 kA |
| Breaking capacity at 690 V | 7.5 kA |
| Power loss, max. | 13.1 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
Where can I buy the 3VA1032-3ED32-0DC0 and how is it quoted?
This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figure is published here.
What are the key interrupting ratings for this MCCB?
The 3VA1032-3ED32-0DC0 clears 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.
What is the continuous current rating at elevated ambient temperatures?
It carries 32 A from 40 °C to 50 °C, derates to 31 A at 55–60 °C, and to 30 A at 65–70 °C.
Does this breaker include an undervoltage release?
Yes, it is equipped with an undervoltage release (UVR) and two auxiliary switches (HQ design) for remote status indication.