Skip to main content
Siemens 3VA1032-3ED36-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-3ED36-0AE0 SENTRON MCCB, 32 A, 75.6 kA at 24

MPN3VA1032-3ED36-0AE0

Siemens SENTRON 3VA1032-3ED36-0AE0, 3-pole molded case circuit breaker, 32 A (40 °C), TM210 thermal-magnetic release, breaking capacity 75.6 kA at 240 V AC, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-3ED36-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10323ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-3ED36-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.10.6 W
3VA1032-3ED36-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1032-3ED36-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-3ED36-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1032-3ED36-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-3ED36-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1032-3ED36-0AE0 — 32 A MCCB with TM210 Release

Its TM210 thermal-magnetic release provides overload and short-circuit protection, with a rated current of 32 A at 40 °C ambient — no derating needed up to 50 °C, then a gentle slope to 30 A at 70 °C.

Breaking capacity is voltage-dependent: 75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Listed as current production.

Integration Notes

Occupies a 76.2 mm wide (3 in) footprint on the DIN rail or panel mount, 130 mm tall, 70 mm deep. Rated insulation voltage 800 V.

Frequently asked questions

Where can I buy 3VA1032-3ED36-0AE0 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What are the key ratings of 3VA1032-3ED36-0AE0?

3-pole, 32 A at 40 °C (derated to 30 A at 70 °C), TM210 thermal-magnetic release, breaking capacity 75.6 kA at 240 V AC down to 7.5 kA at 690 V AC, rated insulation voltage 800 V.

Will 3VA1032-3ED36-0AE0 drop into a panel specified for 3VA1110-5ED36-0AC0?

The 3VA1110-5ED36-0AC0 is a different frame size (100 A class) — the 3VA1032 is a 32 A frame. Panel cutouts, bus connections, and thermal ratings differ. Verify footprint compatibility against your panel layout before substitution.

MPN
3VA1032-3ED36-0AE0