Skip to main content
Siemens 3VA1032-3ED36-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-3ED36-0DA0 SENTRON MCCB, 32 A, 3-Pole, TM210

MPN3VA1032-3ED36-0DA0

Siemens SENTRON 3VA1032-3ED36-0DA0, 3-pole molded case circuit breaker, 32 A rated continuous current (Iu), TM210 thermal-magnetic release, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1032-3ED36-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1032-3ED36-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1032-3ED36-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1032-3ED36-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1032-3ED36-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1032-3ED36-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1032-3ED36-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What the ratings mean for fit

The 3VA1032-3ED36-0DA0 is a 3-pole SENTRON MCCB rated for 32 A continuous at 40 °C, and it holds that rating flat through 50 °C — only starts derating above 55 °C, where it drops to 30.72 A, then 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. That thermal curve means a panel running at 50 °C ambient still gets full 32 A capacity; no need to oversize for a warm enclosure. The interrupting ratings climb with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. For a 480 V distribution panel, that 32 kA at 440 V figure is the one that governs SCCR coordination — check your available fault current against that value. The TM210 thermal-magnetic release handles line protection, no communication module or phase-failure detection on this variant.

Panel integration

Mounts on a DIN rail or panel-mount base — the 70 mm depth, 76.2 mm width, and 130 mm height fit standard SENTRON 3VA footprint. IP40 on the front means it's protected against tools and small wires entering the face, but it's not sealed for washdown; keep it inside a panel enclosure. The 800 V rated insulation voltage (Ui) covers most low-voltage distribution up to 690 V line-to-line. No auxiliary contact version fitted on this order code — if you need status feedback, you'll add a separate auxiliary switch block.

Frequently asked questions

Where can I buy 3VA1032-3ED36-0DA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What are the key interrupting ratings for this MCCB?

At 240 V it interrupts 75.6 kA; at 415 V, 52.5 kA; at 440 V, 32 kA; and at 690 V, 7.5 kA. The 440 V figure is the one to check for 480 V panel SCCR coordination.

Will 3VA1032-3ED36-0DA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

Both are SENTRON 3VA frame MCCBs with the same 70 mm depth, 76.2 mm width, and 130 mm height footprint, so mechanical fit is identical. The key difference is the continuous rating: this one is 32 A versus the 3VA1010's lower rating. Check that the load and upstream protection are sized for 32 A before swapping.

MPN
3VA1032-3ED36-0DA0