Skip to main content
Siemens 3VA1032-3ED36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-3ED36-0HC0 SENTRON MCCB, 32 A, 75.6 kA at 24

MPN3VA1032-3ED36-0HC0

Siemens SENTRON, Molded case circuit breaker, 3VA1032-3ED36-0HC0, 3-pole, 32 A, TM210 thermal-magnetic release, 75.6 kA at 240 V, shunt trip STL, 2 HQ auxiliary switches, IP40 front, current lifecycle.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1032-3ED36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1032-3ED36-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1032-3ED36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1032-3ED36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1032-3ED36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1032-3ED36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1032-3ED36-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1032-3ED36-0HC0 — 32 A MCCB with TM210 Release

The Siemens SENTRON 3VA1032-3ED36-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for 32 A continuous current at 40 °C, with a TM210 thermal-magnetic release. It carries a 75.6 kA interrupting capacity at 240 V, stepping down to 52.5 kA at 415 V and 32 kA at 440 V — sufficient for most distribution panel fault levels downstream of a transformer. The 800 V rated insulation voltage (Ui) and the IP40 front protection suit it for installation in a standard switchgear enclosure with a gland plate above. This MCCB is configured for line protection (not motor or generator duty) and includes a factory-integrated shunt trip (STL) release for remote tripping. The auxiliary contact block carries 2 HQ (high-availability) switches, useful for signaling breaker status back to a PLC or SCADA. The mechanical endurance is rated at 15,000 operations, typical for a panel feeder application where it cycles a few times a year for maintenance isolation.

Thermal Derating and Ambient Temperature

The 32 A rating holds flat from 40 °C through 50 °C, then derates linearly: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. If the panel ambient runs above 50 °C — say a sealed enclosure near a furnace line — size the load side for the derated figure, not the nameplate 32 A. The operating temperature range spans -25 °C to 70 °C; storage limits are -40 °C to 80 °C.

Dimensions and Panel Fit

The breaker measures 130 mm high, 76.2 mm wide (3-module footprint on a 25 mm grid), and 70 mm deep. The 70 mm depth is the body only — add clearance for the rear terminals and the shunt trip wiring. It fits a standard DIN-rail or screw-mounted panel backplate. The IP40 front means no gasketed door seal; the panel door must provide its own environmental protection if washdown is required.

Frequently asked questions

Who supplies 3VA1032-3ED36-0HC0 and how is it quoted for volume purchases?

We source this part through our independent distribution network. For volume pricing and lead time, submit an RFQ — availability is confirmed at quote time, not on this page.

What compliance documentation does this brand provide for 3VA1032-3ED36-0HC0?

The SENTRON series typically carries UL, CSA, CE, and CCC certifications; specific documentation (RoHS, REACH, IEC) is available upon request with the order.

What is 3VA1032-3ED36-0HC0's interrupting capacity at different voltages?

It is rated 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the high 240 V figure suits it for 277/480 V distribution where the fault current is highest at the line side.

MPN
3VA1032-3ED36-0HC0