Skip to main content
Siemens 3VA1032-4ED32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-4ED32-0AD0 SENTRON MCCB, 32 A, 3-Pole, 121 k

MPN3VA1032-4ED32-0AD0

Siemens SENTRON 3VA1032-4ED32-0AD0, molded case circuit breaker, 3-pole, 32 A rated continuous current, TM210 thermal-magnetic release, 121 kA at 240 V interrupting capacity, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1032-4ED32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1032-4ED32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1032-4ED32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1032-4ED32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1032-4ED32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1032-4ED32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1032-4ED32-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Line protection MCCB with high interrupting capacity

The Siemens SENTRON 3VA1032-4ED32-0AD0 is a 3-pole molded case circuit breaker rated for 32 A continuous current at 40 °C, using a TM210 thermal-magnetic overcurrent release. Its interrupting capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, making it suitable for high-fault-current panelboards and distribution boards where a standard MCB would not hold. The 800 V rated insulation voltage (Ui) confirms it can be used in 480Y/277 V and 600 V delta systems with adequate clearance.

What the ratings mean for fit

The 32 A rating holds flat from 40 °C to 50 °C — no derating needed in a typical 40 °C panel ambient. Above 50 °C it drops to 30.72 A at 55 °C and 28.8 A at 70 °C, which matters if this breaker sits near heat sources or in a non-ventilated enclosure. The 121 kA at 240 V figure governs its use on the secondary side of a 208Y/120 V transformer or a 240 V delta service; at 480 V the available fault current must be below 75.6 kA, and at 600 V class (690 V rated) the limit is 11.9 kA. The TM210 release is fixed thermal and magnetic — no field-adjustable trip settings, so the breaker is selected for a specific load current, not tuned on site.

Panel integration and mechanical fit

At 76.2 mm wide, 130 mm tall, and 70 mm deep, this MCCB occupies a standard 3-pole footprint for the SENTRON 3VA platform. The IP40 front protection means it is suitable for enclosed panel mounting where tools or fingers cannot contact live parts. Three auxiliary switches (HQ type) are integrated for status feedback to a PLC or remote indication — no separate aux kit to order. The 15 000-cycle latching endurance (mechanical) suits applications with occasional switching, not daily load-break duty.

Frequently asked questions

Where can I buy 3VA1032-4ED32-0AD0?

This MCCB is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What interrupting capacity does this MCCB have at 240 V?

121 kA at 240 V, which covers high-fault-current services where a standard 10 kA or 25 kA breaker would not suffice.

Will 3VA1032-4ED32-0AD0 drop into a panel specified for 3VA1010-2ED42-0AE0?

Both are 3-pole SENTRON 3VA breakers sharing the same 76.2 mm width and 130 mm height, so the mechanical footprint matches. The key difference is the continuous current rating — 32 A here versus the 10 A of the peer — so the bus bar and downstream conductor sizing must be verified for the higher rating.

What compliance documentation does Siemens provide for this MCCB?

Siemens SENTRON 3VA breakers carry UL, CSA, and IEC certifications per standard product documentation. RoHS and REACH declarations are available through Siemens Industry Online Support. Specific certificate numbers are not listed in this spec summary.

MPN
3VA1032-4ED32-0AD0