The Siemens SENTRON 3VA1032-4ED32-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated 32 A continuous at 40 °C ambient, with a maximum breaking capacity of 121 kA at 240 V AC.
The interrupting rating drops as line voltage rises: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Rated 32 A from 40 °C through 50 °C, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C. If the panel internal temperature exceeds 50 °C, you lose 1–2 A of headroom — factor that into the load schedule.