It holds that rating flat from 40 °C through 50 °C; above 50 °C the thermal curve begins to derate, dropping to 28.8 A by 70 °C. Breaking capacity reaches 121 kA at 240 VAC, 75.6 kA at 415 VAC, and 52.5 kA at 440 VAC — numbers that tell you it is sized for high-fault panels where a standard MCB would weld shut. The TM210 thermal-magnetic release handles the overcurrent trip, and an undervoltage release (UVR) is built in. Two auxiliary switches (HQ type) ride on the side, so you get a status signal back to the PLC without adding a separate contact block. Footprint is 76.2 mm wide, 130 mm tall, 70 mm deep — standard three-pole MCCB width for a 32 A frame.

Siemens 3VA1032-4ED32-0BC0 SENTRON MCCB, 32 A, 121 kA at 240
Siemens SENTRON 3VA1032-4ED32-0BC0, molded case circuit breaker, 3-pole, 32 A rated continuous current Iu, line protection, 121 kA breaking capacity at 240 V, 70 mm depth, 76.2 mm width, 130 mm height.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 32 A |
| Current at 45 °C | 32 A |
| Current at 50 °C | 32 A |
| Current at 55 °C | 30.72 A |
| Current at 60 °C | 30.08 A |
| Current at 65 °C | 29.44 A |
| Current at 70 °C | 28.8 A |
| Switching capacity class | S |
| Breaking capacity at 240 V | 121 kA |
| Breaking capacity at 415 V | 75.6 kA |
| Breaking capacity at 440 V | 52.5 kA |
| Breaking capacity at 690 V | 11.9 kA |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Parameter | Value |
|---|---|
| Main circuit connection type | lug terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |