Its interrupting capacity hits 121 kA at 240 V and 75.6 kA at 415 V, so it handles high-fault-current scenarios without cascading upstream.
Rated for 32 A continuously up to 50 °C ambient, derating to 30 A at 70 °C. If your enclosure runs hot near the top of that range, size the breaker one frame up or add ventilation.
Interrupting capacity by voltage
At 240 V: 121 kA; at 415 V: 75.6 kA; at 440 V: 52.5 kA; at 500 V: 11.9 kA; at 690 V: 11.9 kA.