Breaking capacity is 121 kA at 240 V AC, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 500 V and 690 V. These figures cover most industrial service-entrance and feeder applications; the 415 V rating is the one to check for 400 V class panels common in European and Asian installations.
Rated current holds at 32 A from 40 °C through 50 °C, then steps to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. Dimensions are 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mount panel layouts. Power loss at rated load is 13.1 W, which adds to the enclosure's thermal budget; account for it when sizing ventilation or forced cooling.