Skip to main content
Siemens 3VA1032-4ED36-0AA0 — Molded Case Circuit Breakers (MCCB)

3VA1032-4ED36-0AA0 SENTRON MCCB, 32 A, 3-pole, line protecti

MPN3VA1032-4ED36-0AA0
Active

Siemens SENTRON 3VA1032-4ED36-0AA0, molded case circuit breaker, 3-pole, 32 A, TM210 overcurrent release, line protection, breaking capacity 121 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-4ED36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1032-4ED36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W
3VA1032-4ED36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1032-4ED36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-4ED36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1032-4ED36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-4ED36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1032-4ED36-0AA0 — 32 A MCCB, line protection

Its TM210 overcurrent release provides fixed thermal-magnetic protection — thermal for overloads, magnetic for short-circuits — with no undervoltage release or trip indicator fitted on this variant. Breaking capacity reaches 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V, giving ample SCCR headroom for most low-voltage distribution applications. Rated insulation voltage is 800 V, and the breaker maintains full 32 A rating up to 50 °C ambient; derating begins at 55 °C (31 A) and reaches 30 A at 70 °C.

Panel fit and thermal management

The breaker occupies 76.2 mm width, 130 mm height, and 70 mm depth — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount enclosures without re-drilling. Maximum power loss is 10.6 W.

No communication function, ground-fault monitoring, or voltage-trigger features are built in — this is a straight line-protection MCCB with no auxiliary electronics.

MPN