Integrator's spec recap — 3VA1032-4ED36-0CC0
It carries a 32 A rating at 40 °C ambient, holding that rating flat through 50 °C before a mild derate to 30 A at 70 °C — useful for warm enclosures without oversizing. Breaking capacity reaches 121 kA at 240 V AC and 75.6 kA at 415 V, so it handles high-fault utility feeds or transformer secondaries.
Rated insulation voltage is 800 V, and the interrupting ratings span the common industrial voltages: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
The MCCB measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA frame footprint that fits existing DIN-rail or screw-mount panel layouts.