Skip to main content
Siemens 3VA1032-4ED36-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-4ED36-0DA0 SENTRON MCCB, 32 A, 3-Pole, 121 k

MPN3VA1032-4ED36-0DA0

Siemens SENTRON 3VA1032-4ED36-0DA0, molded case circuit breaker, 3-pole, 32 A rated continuous Iu, TM210 thermal-magnetic release, 121 kA at 240 V interrupting capacity, line protection version, undervoltage release fitted, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1032-4ED36-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1032-4ED36-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1032-4ED36-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1032-4ED36-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1032-4ED36-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1032-4ED36-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1032-4ED36-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens SENTRON 3VA1032-4ED36-0DA0 — 32 A MCCB with TM210 Release

The Siemens SENTRON 3VA1032-4ED36-0DA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 32 A and a rated insulation voltage Ui of 800 V. It uses a TM210 thermal-magnetic overcurrent release and is fitted with an undervoltage release (UVR). This MCCB is part of the SENTRON family, designed for panel OEM integration on a DIN rail or mounting plate. The front face carries an IP40 protection class, meaning it is protected against tools and wires over 1 mm — standard for enclosed distribution boards. No auxiliary contact version is fitted, and there is no communication function, phase failure detection, or ground fault monitoring on this variant; it is a straight line-protection breaker with undervoltage release only.

Current Derating and Thermal Performance

The 32 A rating holds flat from 40 °C through 50 °C ambient. Above that, the thermal curve begins to derate: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. For a panel OEM wireman packing breakers into a high-fill-factor enclosure, this means the 3VA1032-4ED36-0DA0 can carry its full 32 A in a 50 °C panel without derating — a common condition in sealed or sun-loaded cabinets. The operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C.

Physical Dimensions and Panel Fit

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep. The width of 76.2 mm is standard for a 3-pole MCCB in this class.

Frequently asked questions

Will 3VA1032-4ED36-0DA0 drop into a panel designed for 3VA1010-2ED32-0JA0?

Both breakers share the same 76.2 mm width and 130 mm height, so the 3VA1032-4ED36-0DA0 fits the same panel cutout. The depth may differ slightly — verify back-panel clearance before committing.

Does 3VA1032-4ED36-0DA0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as the auxiliary release. The design of the auxiliary release is specifically an undervoltage release (UVR). No auxiliary contact version is included.

MPN
3VA1032-4ED36-0DA0