Skip to main content
Siemens 3VA1040-2ED32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1040-2ED32-0BH0 SENTRON MCCB, 40 A, 3-pole, TM210

MPN3VA1040-2ED32-0BH0

Siemens SENTRON 3VA1040-2ED32-0BH0, molded case circuit breaker, 3-pole, 40 A rated continuous current, TM210 thermal-magnetic release, 52.5 kA interrupting at 240 V, with integrated undervoltage release and 2 aux + 1 trip alarm HQ contacts.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1040-2ED32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1040-2ED32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1040-2ED32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1040-2ED32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1040-2ED32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1040-2ED32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1040-2ED32-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1040-2ED32-0BH0 is a 3-pole molded case circuit breaker rated for 40 A continuous current at 40 °C, with a TM210 thermal-magnetic release for line protection. Its interrupting capacity hits 52.5 kA at 240 V and 32 kA at 415 V, so it handles high-fault commercial and industrial panel feeds without cascading upstream. The integrated undervoltage release (UVR) drops the breaker if control voltage is lost — a common requirement for safety circuits and emergency-stop chains.

Rated 40 A from 40 °C up through 50 °C, then it begins to taper: 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, 36 A at 70 °C.

MPN
3VA1040-2ED32-0BH0