Skip to main content
Siemens 3VA1040-2ED32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1040-2ED32-0CA0 SENTRON MCCB, 40 A, 3-Pole, Line

MPN3VA1040-2ED32-0CA0

Siemens SENTRON 3VA1040-2ED32-0CA0, molded case circuit breaker, 3-pole, 40 A, TM210 thermal-magnetic release, line protection, IP40 front, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1040-2ED32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1040-2ED32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1040-2ED32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1040-2ED32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1040-2ED32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1040-2ED32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1040-2ED32-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1040-2ED32-0CA0 is a SENTRON molded case circuit breaker (MCCB) rated for 40 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release for line protection in a 3-pole configuration. Its interrupting capacity reaches 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — these are the fault levels it can safely clear at the respective system voltages, which decides whether it holds on a high-fault panelboard or needs an upstream current-limiting fuse.

Sizing and derating for panel fit

The breaker measures 70 mm deep, 76.2 mm wide, and 130 mm high — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mount panel layouts without requiring a gland-plate rework. Rated continuous current holds at 40 A from 40 °C through 50 °C; above that it derates to 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C.

The integrated auxiliary trip is listed separately as order code 3VA9608-0BB24; if you need that spare, order it alongside the breaker.

Frequently asked questions

Does the 3VA1040-2ED32-0CA0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as the auxiliary release, which trips the breaker when control voltage drops below the dropout threshold.

What is the depth of the 3VA1040-2ED32-0CA0?

The depth is 70 mm, with a width of 76.2 mm and a height of 130 mm.

MPN
3VA1040-2ED32-0CA0