Skip to main content
Siemens 3VA1040-2ED32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1040-2ED32-0DC0 SENTRON MCCB, 40 A, 52.5 kA

MPN3VA1040-2ED32-0DC0

Siemens SENTRON 3VA1040-2ED32-0DC0, Molded case circuit breaker, 3-pole, 40 A, TM210 release, line protection, 52.5 kA at 240 V, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1040-2ED32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1040-2ED32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1040-2ED32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1040-2ED32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1040-2ED32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1040-2ED32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1040-2ED32-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1040-2ED32-0DC0 is a 3-pole molded case circuit breaker rated for 40 A continuous current at 40 °C, with the TM210 thermal-magnetic release for line protection duty. At 240 V it interrupts 52.5 kA; at 415 V it handles 32 kA; at 440 V it drops to 13.6 kA; at 690 V it still holds 7.5 kA. It carries the full 40 A up to 50 °C; at 55 °C it derates to 38.4 A, at 60 °C to 37.6 A, at 65 °C to 36.8 A, and at 70 °C to 36 A. That is a straight thermal limit — no need to guess the ambient correction factor.

Built-in undervoltage release and auxiliary switches

The auxiliary switches are factory-fitted; no field-add kit needed. The rated continuous current Iu is 40 A; the TM210 release is matched to that value.

Frequently asked questions

Does 3VA1040-2ED32-0DC0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) factory-installed, plus two auxiliary switches (HQ type) for remote status indication.

MPN
3VA1040-2ED32-0DC0