Skip to main content
Siemens 3VA1040-3ED36-0CA0 — Molded Case Circuit Breakers (MCCB)

3VA1040-3ED36-0CA0 SENTRON MCCB, 40 A, 3-pole, TM210, UVR

MPN3VA1040-3ED36-0CA0

Siemens SENTRON 3VA1040-3ED36-0CA0, 3-pole molded case circuit breaker, 40 A (40 °C), TM210 release, 75.6 kA at 240 V, undervoltage release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1040-3ED36-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10403ED360AA0
3VA1040-3ED36-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.13.3 W
3VA1040-3ED36-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1040-3ED36-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1040-3ED36-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1040-3ED36-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1040-3ED36-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Rated 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 500 V and 690 V. The 75.6 kA at 240 V covers high-fault utility feeds in North American panels; the 52.5 kA at 415 V handles European 400 V distribution.

At 55 °C it derates to 38.4 A, at 60 °C to 37.6 A, at 65 °C to 36.8 A, and at 70 °C to 36 A.

Width 76.2 mm (3 in), height 130 mm (5.12 in), depth 70 mm (2.76 in).

Frequently asked questions

What is the breaking capacity of 3VA1040-3ED36-0CA0 at 415 V?

52.5 kA at 415 V, which covers standard European 400 V distribution panel fault levels.

Where can I buy 3VA1040-3ED36-0CA0?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What does the TM210 release mean on this breaker?

TM210 is a fixed thermal-magnetic release — the thermal and magnetic trip settings are factory-set and not field-adjustable. The breaker is sized at order for the intended load.

What is the rated insulation voltage of 3VA1040-3ED36-0CA0?

Rated insulation voltage is 800 V, allowing application in 690 V systems with full margin.

MPN
3VA1040-3ED36-0CA0