Skip to main content
Siemens 3VA1050-2ED32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-2ED32-0CA0 SENTRON MCCB, 50 A, 3-Pole, Line

MPN3VA1050-2ED32-0CA0

Siemens SENTRON 3VA1050-2ED32-0CA0, molded case circuit breaker, 3-pole, 50 A rated continuous current, line protection, TM210 thermal-magnetic trip unit, 52.5 kA breaking capacity at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1050-2ED32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1050-2ED32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1050-2ED32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1050-2ED32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-2ED32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1050-2ED32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-2ED32-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1050-2ED32-0CA0 — 50 A MCCB with TM210 Trip Unit

Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The 690 V rating of 7.5 kA is relevant for 690 V drives or mining applications where fault levels are lower.

The 76.2 mm width is a standard 3-pole MCCB footprint that fits a 4-module (4 x 18 mm) DIN-rail space. The 70 mm depth keeps the breaker within typical 200 mm enclosure depths, leaving room for wiring gutters and busbar connections behind the panel door. No auxiliary contact or communication module is fitted as standard; the UVR is the only integrated release.

Derating begins at 55 °C (48 A), dropping to 45 A at 70 °C. For a panel with internal temperature rise, this means the breaker can be loaded to nameplate at 50 °C without margin — a common condition in sealed enclosures with multiple devices.

Frequently asked questions

What is the breaking capacity of 3VA1050-2ED32-0CA0 at 415 V?

The breaking capacity at 415 V is 32 kA. At 240 V it is 52.5 kA, at 440 V it is 13.6 kA, and at 690 V it is 7.5 kA.

Where can I buy 3VA1050-2ED32-0CA0 and how is it quoted?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does 3VA1050-2ED32-0CA0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release design. The UVR will trip the breaker if control voltage drops below the release threshold.

MPN