SENTRON 3VA1050-2ED36-0AH0 — 50 A MCCB with TM210 release
Breaking capacity is specified across four voltage levels: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The breaker holds full 50 A up to 50 °C, then drops to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.
Panel fit and auxiliary contacts
That gives two form-C signals for status feedback and a separate alarm contact that changes state only on a trip event — useful for remote annunciation without wiring through the breaker handle position. Front protection is IP40, adequate for clean indoor panel environments.