Skip to main content
Siemens 3VA1050-2ED36-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-2ED36-0BC0 SENTRON MCCB, 50 A, 3-Pole, Line

MPN3VA1050-2ED36-0BC0

Siemens SENTRON 3VA1050-2ED36-0BC0, molded case circuit breaker, 3-pole, 50 A rated continuous current, line protection version with TM210 thermal-magnetic release, 52.5 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-2ED36-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1050-2ED36-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1050-2ED36-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1050-2ED36-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-2ED36-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1050-2ED36-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-2ED36-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What ships in the carton

The Siemens SENTRON 3VA1050-2ED36-0BC0 is a 3-pole molded case circuit breaker rated for 50 A continuous current (Iu) with a TM210 thermal-magnetic overcurrent release. It ships with 2 auxiliary switches (HQ version) and an integrated undervoltage release (UVR) — the auxiliary trip module is order code 3VA9608-0BB11, already fitted. No communication module, no voltage trigger, no ground-fault monitoring on this variant. Front protection is IP40; the unit is sized for DIN-rail or panel-mount integration at 70 mm deep, 76.2 mm wide, 130 mm tall.

Interrupting capacity and thermal derating

Interrupting capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — these are the maximum fault currents the breaker can safely clear at each voltage level. The TM210 release holds 50 A continuous up to 50 °C ambient; above that it derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. Rated insulation voltage is 800 V. Latching endurance is rated at 15,000 operations.

Frequently asked questions

How do I get current pricing and availability for 3VA1050-2ED36-0BC0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and stock are confirmed at quote time.

What is 3VA1050-2ED36-0BC0's interrupting capacity at 415 V?

32 kA at 415 V, with higher ratings at lower voltages (52.5 kA at 240 V) and lower at higher voltages (13.6 kA at 440 V, 7.5 kA at 690 V).

Does this MCCB include an undervoltage release?

Yes, it ships with an integrated undervoltage release (UVR) as standard. The auxiliary trip module is order code 3VA9608-0BB11, already fitted.

What compliance documentation does this brand provide for 3VA1050-2ED36-0BC0?

The part carries a DIN EN 81346-2 reference code (Q) and is designed to IEC/EN 60947-2 standards for molded case circuit breakers. Standard Siemens documentation includes the device manual and declaration of conformity; specific RoHS/REACH/UL documentation is available on request at quote time.

MPN