Rated 50 A continuous at 40 °C, it holds that same 50 A all the way up to 50 °C and only starts to derate above 55 °C (-), so it handles warm panel environments without a lot of headroom loss. Interrupting capacity runs 52.5 kA at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V — numbers that tell you it's built for high-fault commercial and light industrial distribution boards, not for sitting behind a transformer secondary that's already current-limited.
Ratings that matter for panel fit
At 70 mm deep, 76.2 mm wide, and 130 mm tall, this MCCB fits a 3-pole footprint. Maximum power loss is 14.6 W.
The trip indicator is present, and there is a voltage trigger — meaning the breaker can signal its state and be remotely tripped via the shunt coil. No undervoltage release is fitted, and there is no ground-fault monitoring or communication function. If you need remote open/close feedback and emergency trip, this unit has it; if you need UVR or ground-fault, look at the -2ED36-0JH0 variants with those options.