Siemens 3VA1050-2ED42-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-2ED42-0AD0 SENTRON MCCB, 4-Pole, 50A, 52.5kA

MPN3VA1050-2ED42-0AD0

Siemens SENTRON 3VA1050-2ED42-0AD0, 4-pole molded case circuit breaker, 50 A at 40 °C, TM210 thermal-magnetic release, line protection, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-2ED42-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10502ED420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1050-2ED42-0AD0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1050-2ED42-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1050-2ED42-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-2ED42-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1050-2ED42-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-2ED42-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

SENTRON 3VA1050-2ED42-0AD0 — Line Protection MCCB

The Siemens 3VA1050-2ED42-0AD0 is a 4-pole molded case circuit breaker from the SENTRON 3VA series, designed for line protection. It carries a TM210 thermal-magnetic release and is rated 50 A continuous at 40 °C ambient, derating to 45 A at 70 °C. Breaking capacity hits 52.5 kA at 240 V and 32 kA at 415 V, so it handles high-fault utility feeds without cascading upstream. Panel builders: the 70 mm depth and 101.6 mm width fit standard SENTRON mounting footprints. Rated insulation voltage is 800 V, and maximum power loss is 14.6 W — factor that into enclosure thermal rise calculations.

Current Rating and Thermal Derating

Full 50 A holds up to 50 °C ambient without derating. At 55 °C it drops to 49 A, at 60 °C to 48 A, at 65 °C to 46 A, and at 70 °C to 45 A. That means in a warm enclosure — say 55 °C internal — you lose 1 A of headroom; at 70 °C you lose 5 A. Size the continuous load against the derated figure for the actual panel temperature, not the 40 °C nameplate.

Breaking Capacity Across Voltages

The interrupting ratings climb as voltage drops: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. For a 480 V delta service (typically 480Y/277), the relevant figure is the 440 V or 500 V column — 13.6 kA or 7.5 kA, respectively. Verify the available fault current at the installation point against these values to confirm SCCR compliance.

Frequently asked questions

What is the breaking capacity of 3VA1050-2ED42-0AD0 at 415 V?

32 kA at 415 V. The full voltage sweep: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Where can I buy 3VA1050-2ED42-0AD0 and get a price?

Sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the TM210 release on this breaker?

TM210 is a thermal-magnetic release — thermal element for overload protection, magnetic element for short-circuit. Fixed thermal rating at 50 A (40 °C ambient) with the derating curve listed above.

MPN