Skip to main content
Siemens 3VA1050-2ED46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-2ED46-0AA0 SENTRON 4-pole MCCB, 50 A, TM210

MPN3VA1050-2ED46-0AA0
Active

Siemens SENTRON 3VA1050-2ED46-0AA0, 4-pole molded case circuit breaker, 50 A, TM210 thermal-magnetic trip, line protection, 70 mm depth, 101.6 mm width, 130 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-2ED46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1050-2ED46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1050-2ED46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1050-2ED46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-2ED46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1050-2ED46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-2ED46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens SENTRON 3VA1050-2ED46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 50 A continuous current, designed for line protection in industrial distribution panels. It carries a TM210 thermal-magnetic trip unit — the thermal element handles overloads, the magnetic element clears short circuits fast. Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. That means it can safely interrupt fault currents up to those levels without welding contacts or rupturing the case — critical for coordinating with upstream gear.

Deployment and integration

Ambient temperature derating is mild: full 50 A up to 50 °C, then 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. In a hot panel near the top of a cabinet, you lose about 10 % capacity — plan your load accordingly.

Lifecycle and sourcing

Rated insulation voltage is 800 V, and the maximum power loss at rated current is 14.6 W — useful for thermal calculations in a sealed enclosure. Storage temperature range is -40 °C to 80 °C; operating range is -25 °C to 70 °C.

MPN
3VA1050-2ED46-0AA0