Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.
Deployment and integration
Ambient temperature derating is mild: full 50 A up to 50 °C, then 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. In a hot panel near the top of a cabinet, you lose about 10 % capacity — plan your load accordingly.