Skip to main content
Siemens 3VA1050-3ED36-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-3ED36-0AD0 SENTRON MCCB, 50A, 75.6kA

MPN3VA1050-3ED36-0AD0

Siemens SENTRON 3VA1050-3ED36-0AD0, 3-pole molded case circuit breaker, 50 A rated continuous current, 75.6 kA breaking capacity at 240 V, TM210 thermal-magnetic release, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-3ED36-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1050-3ED36-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1050-3ED36-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1050-3ED36-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-3ED36-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1050-3ED36-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-3ED36-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity and selectivity

The 3VA1050-3ED36-0AD0: Rated short-circuit breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the 240 V figure is the standout for North American 277/480 V panels where the line-to-neutral fault current can be high. At 415 V, 52.5 kA gives headroom for most industrial main feeders without cascading upstream. The 690 V rating (7.5 kA) is lower but still covers the majority of 690 V motor branch faults. The rated insulation voltage Ui is 800 V, so the breaker is insulated for 690 V systems with margin.

Thermal derating and ambient limits

Rated current holds at 50 A from 40 °C through 50 °C, then steps down: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, 45 A at 70 °C. That's a shallow derating curve — only 10 % drop from 40 °C to 70 °C — so it's stable in warm enclosures. Operating ambient range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — fits standard 3-pole MCCB panel cutouts. Front protection is IP40, so keep it inside a panel, not in a washdown zone.

Auxiliary contacts and release options

Comes fitted with 3 auxiliary switches (HQ type) for status feedback to a PLC or annunciator panel — no separate auxiliary release module needed for basic signalling. The TM210 release is the standard thermal-magnetic type; no ground-fault monitoring or undervoltage release on this order code. Mechanical endurance is rated at 15,000 operations, typical for a line-protection MCCB in secondary distribution.

Frequently asked questions

Where can I buy 3VA1050-3ED36-0AD0 and get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What are the key dimensions of the 3VA1050-3ED36-0AD0?

Height is 130 mm, width is 76.2 mm, depth is 70 mm — standard 3-pole MCCB footprint for panel mounting.

MPN
3VA1050-3ED36-0AD0