Skip to main content
Siemens 3VA1050-3ED36-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1050-3ED36-0JC0 MCCB, 50 A, 75.6 kA at 24

MPN3VA1050-3ED36-0JC0

Siemens SENTRON 3VA1050-3ED36-0JC0, molded case circuit breaker, 3-pole, 50 A (40 °C), 75.6 kA at 240 V, line protection, with shunt trip and 2 auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-3ED36-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10503ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1050-3ED36-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1050-3ED36-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1050-3ED36-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-3ED36-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1050-3ED36-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-3ED36-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1050-3ED36-0JC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection duty. It carries 50 A continuously at 40 °C and delivers a 75.6 kA interrupting capacity at 240 VAC — enough to handle high-fault utility feeds or transformer secondaries in a distribution panel.

Key ratings and what they mean for fit

The 50 A rating holds steady from 40 °C through 50 °C, then derates to 49 A at 55 °C and 45 A at 70 °C — useful to know if the breaker sits near other heat sources in a crowded enclosure. The 75.6 kA at 240 V is the headline fault-clearing number; at 415 V it still breaks 52.5 kA, and at 690 V it holds 7.5 kA. That means it can be applied on 480 V delta or 600 V wye systems as long as the available fault current stays under the published curve. Rated insulation voltage is 800 V, so the breaker's internal clearance and creepage are designed for 690 V line-to-line systems with margin. The 3-pole construction fits standard three-phase feeders — motor branch circuits, lighting panels, or sub-feed distribution.

Built-in accessories and panel integration

This variant ships with a shunt trip (STL) release and two auxiliary switches (HQ type) factory-installed. The shunt trip allows remote tripping from a PLC or emergency-stop circuit; the auxiliary switches provide status feedback — open/closed indication to a control system or indicator lamp. No field-add-on kit needed for these functions. Dimensions are 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits SENTRON panelboards and most DIN-rail adapters.

MPN
3VA1050-3ED36-0JC0