Skip to main content
Siemens 3VA1050-4ED32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-4ED32-0CA0 SENTRON MCCB, 50 A, 3-Pole, Line

MPN3VA1050-4ED32-0CA0

Siemens SENTRON 3VA1050-4ED32-0CA0, molded case circuit breaker, 3-pole, 50 A rated continuous current, line protection, TM210 overcurrent release, 121 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1050-4ED32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1050-4ED32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1050-4ED32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1050-4ED32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-4ED32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1050-4ED32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-4ED32-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1050-4ED32-0CA0 — SENTRON MCCB, 50 A, Line Protection with Undervoltage Release

Breaking capacity is specified across four voltage levels: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. These figures cover the fault-current range for most industrial distribution panels; the 121 kA at 240 V is particularly relevant for high-fault installations in North American 240/120 V split-phase or 240 V three-phase services.

Sourcing and Lifecycle — Active Production, Quoted to Order

No alternate or successor part is listed; the part is the current production variant.

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard SENTRON 3VA footprint that fits DIN-rail or screw-mount panel layouts. The 70 mm depth allows clearance in shallow enclosures where deeper MCCBs would conflict with gland plates or backplane wiring. No auxiliary contact is fitted as standard; the UVR is the only integrated release. If remote status signaling is needed, the auxiliary contact kit (order code 3VA9608-0BB24) can be added in the field.

Frequently asked questions

Where can I buy 3VA1050-4ED32-0CA0 and get a price?

This MCCB is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at different voltages?

Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. The 121 kA rating at 240 V covers high-fault installations in North American services.

Does this breaker include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as standard. The UVR trips the breaker when the supply voltage drops below the release threshold, providing automatic disconnection on loss of control voltage.

What are the physical dimensions of 3VA1050-4ED32-0CA0?

Height is 130 mm, width is 76.2 mm, and depth is 70 mm. The 70 mm depth fits shallow enclosures where deeper breakers would not clear gland plates or backplane wiring.

MPN
3VA1050-4ED32-0CA0