Breaking capacity reaches 121 kA at 240 V AC and 75.6 kA at 415 V AC, so it handles high-fault utility feeds or transformer-secondaries without cascading upstream. Front protection is IP40, meaning it keeps tools and fingers out but isn't sealed against washdown — panel-mount only, no outdoor exposure.
Above that it derates: 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, 45 A at 70 °C.
Panel fit — dimensions and auxiliaries