Skip to main content
Siemens 3VA1050-4ED36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-4ED36-0AH0 SENTRON MCCB, 50A, 3-Pole, TM210

MPN3VA1050-4ED36-0AH0

Siemens SENTRON 3VA1050-4ED36-0AH0, molded case circuit breaker, 3-pole, 50 A rated current, TM210 thermal-magnetic release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-4ED36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10504ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1050-4ED36-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1050-4ED36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1050-4ED36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-4ED36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1050-4ED36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-4ED36-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1050-4ED36-0AH0 – 50 A MCCB, TM210 Release, Line Protection

The Siemens 3VA1050-4ED36-0AH0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection, rated at 50 A at 40 °C with a TM210 thermal-magnetic release. It carries a breaking capacity of 121 kA at 240 V and 75.6 kA at 415 V, making it suited for high-fault-current industrial distribution panels where selectivity and SCCR headroom are critical. The TM210 release provides fixed thermal and magnetic trip settings — the thermal element handles overloads, the magnetic element clears short-circuits. This is a line-protection design, not a motor-protection or ground-fault variant, so it goes on feeder or branch circuits where the load is resistive or general-purpose, not on individual motor starters requiring adjustable overloads.

Key Ratings and What They Mean for Panel Fit

Rated current holds at 50 A from 40 °C through 50 °C ambient, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. In a warm enclosure — say a non-ventilated panel near a curing press or furnace — the 50 °C rating is the one to size against; at 70 °C you lose 5 A of headroom. Breaking capacity drops with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. For a 480 V panel (common in North American industrial), the 52.5 kA at 440 V is the closest published figure; the 11.9 kA at 500 V and 690 V means this breaker is not the first choice for 600 V class installations unless the available fault current is well under 12 kA. Rated insulation voltage is 800 V, and the breaker carries 3 poles with a TM210 release. It ships with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), which covers status feedback to a PLC or annunciator without needing a separate aux block. Maximum power loss is 14.6 W per pole — figure about 44 W total heat dissipated inside the enclosure at full load. That matters for thermal budgeting in a sealed stainless steel panel on a food line or a crowded cabinet with multiple breakers stacked.

Integration Notes

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth. The 3-pole footprint fits standard Siemens SENTRON 3VA panelboard and distribution-block mounting; no special adapter plate needed for a DIN-rail enclosure if the rail is sized for the 76.2 mm width. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The breaker is rated for the full industrial ambient span — no cold-start derating required down to -25 °C.

Frequently asked questions

What does the TM210 release designation mean?

TM210 is a fixed thermal-magnetic release — the thermal element is non-adjustable, the magnetic pickup is fixed. It is designed for line (feeder) protection, not for motor circuits that need adjustable overloads.