Skip to main content
Siemens 3VA1050-4ED42-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-4ED42-0HA0 SENTRON MCCB, 50 A, 4-Pole, 121 k

MPN3VA1050-4ED42-0HA0

Siemens SENTRON 3VA1050-4ED42-0HA0, molded case circuit breaker, 4-pole, 50 A, line protection, TM210 overcurrent release, 121 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1050-4ED42-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1050-4ED42-0HA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1050-4ED42-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1050-4ED42-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1050-4ED42-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1050-4ED42-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1050-4ED42-0HA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

MCCB for main feeder or large branch — 50 A continuous, 4-pole, with shunt trip

The Siemens 3VA1050-4ED42-0HA0 is a SENTRON molded case circuit breaker rated for 50 A continuous current at 40 °C, with a 4-pole configuration and a TM210 thermal-magnetic overcurrent release. It carries a 121 kA interrupting rating at 240 V and 75.6 kA at 415 V, making it suitable for high-fault-capacity main feeders or large branch circuits in industrial switchboards and panelboards. The front-face IP40 rating means it is protected against solid objects over 1 mm but not sealed against moisture — standard for indoor panel mounting.

Interrupting capacity and thermal derating — what the numbers mean for your panel

The 121 kA interrupting rating at 240 V and 75.6 kA at 415 V give this MCCB headroom for high-fault installations where upstream transformer capacity is large. At 690 V the rating drops to 11.9 kA — still adequate for most 690 V industrial loads, but verify the available fault current at that voltage. The TM210 release holds 50 A continuously from 40 °C up to 50 °C; above that it derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. For a panel running at 55 °C ambient, the effective continuous rating is 48 A, not the nameplate 50 A.

Shunt trip included — no auxiliary contacts, no communication

This variant ships with a shunt trip release (STL) for remote tripping, ordered separately as 3VA9688-0BL30. It does not include undervoltage release, auxiliary contacts, phase failure detection, ground fault monitoring, or communication functions. The N-conductor protection is also omitted. For applications requiring remote status feedback or ground fault protection, a different 3VA variant or an add-on accessory kit is needed.

Lifecycle and sourcing — current production, quoted to order

The lifecycle stage is listed as current production. This MCCB is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time. No official successor has been announced; the 3VA family remains the active SENTRON platform for molded case breakers.

Frequently asked questions

Where can I buy 3VA1050-4ED42-0HA0 and how is it quoted?

This MCCB is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quotation.

What is the interrupting capacity of 3VA1050-4ED42-0HA0 at different voltages?

The interrupting rating is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

What is the rated continuous current and how does it derate with temperature?

Rated continuous current Iu is 50 A. It holds 50 A from 40 °C to 50 °C, then derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

MPN
3VA1050-4ED42-0HA0