Skip to main content
Siemens 3VA1050-4ED42-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-4ED42-0HA0 SENTRON MCCB, 50 A, 4-Pole, 121 k

MPN3VA1050-4ED42-0HA0

Siemens SENTRON 3VA1050-4ED42-0HA0, molded case circuit breaker, 4-pole, 50 A, line protection, TM210 overcurrent release, 121 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1050-4ED42-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1050-4ED42-0HA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C48 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1050-4ED42-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1050-4ED42-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-4ED42-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1050-4ED42-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-4ED42-0HA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

MCCB for main feeder or large branch — 50 A continuous, 4-pole, with shunt trip

The Siemens 3VA1050-4ED42-0HA0 is a SENTRON molded case circuit breaker rated for 50 A continuous current at 40 °C, with a 4-pole configuration and a TM210 thermal-magnetic overcurrent release. It carries a 121 kA interrupting rating at 240 V and 75.6 kA at 415 V, making it suitable for high-fault-capacity main feeders or large branch circuits in industrial switchboards and panelboards.

The 121 kA interrupting rating at 240 V and 75.6 kA at 415 V give this MCCB headroom for high-fault installations where upstream transformer capacity is large. The TM210 release holds 50 A continuously from 40 °C up to 50 °C; above that it derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. For a panel running at 55 °C ambient, the effective continuous rating is 48 A, not the nameplate 50 A.

Shunt trip included — no auxiliary contacts, no communication

It does not include undervoltage release, auxiliary contacts, phase failure detection, ground fault monitoring, or communication functions. The N-conductor protection is also omitted. For applications requiring remote status feedback or ground fault protection, a different 3VA variant or an add-on accessory kit is needed.

Lifecycle and sourcing — current production, quoted to order

No official successor has been announced; the 3VA family remains the active SENTRON platform for molded case breakers.

Frequently asked questions

Where can I buy 3VA1050-4ED42-0HA0 and how is it quoted?

This MCCB is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quotation.

What is the interrupting capacity of 3VA1050-4ED42-0HA0 at different voltages?

The interrupting rating is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

What is the rated continuous current and how does it derate with temperature?

Rated continuous current Iu is 50 A. It holds 50 A from 40 °C to 50 °C, then derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

MPN
3VA1050-4ED42-0HA0