Skip to main content
Siemens 3VA1050-4ED42-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-4ED42-0JA0 SENTRON MCCB, 50A, 4-Pole, 121kA

MPN3VA1050-4ED42-0JA0

Siemens SENTRON 3VA1050-4ED42-0JA0, molded case circuit breaker, 4-pole, 50 A rated, TM210 thermal-magnetic release, shunt trip, 121 kA at 240 VAC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1050-4ED42-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10504ED420AA0
3VA1050-4ED42-0JA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W
3VA1050-4ED42-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1050-4ED42-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-4ED42-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1050-4ED42-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-4ED42-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

It carries a 50 A continuous rating across the 40 °C to 50 °C ambient range, then begins to derate: 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. That means in a hot panel you lose headroom fast — plan your load at 45 A if the enclosure sits near its upper operating limit. The TM210 overcurrent release is a thermal-magnetic type — thermal element for overload protection, magnetic coil for short-circuit response. At 240 V it interrupts 121 kA; at 415 V it drops to 75.6 kA; at 440 V it is 52.5 kA; at 500 V and 690 V it holds at 11.9 kA.

Shunt trip and physical fit

The shunt trip is factory-installed; no field retrofit. There is no undervoltage release on this unit, so a loss of control power does not automatically open the breaker. The 4-pole width is wider than a 3-pole frame — verify the DIN-rail or mounting-plate space before committing the panel layout. The supplied basic switch is order code 3VA10504ED420AA0, which is the internal switching mechanism; the complete breaker ships as one assembly.

MPN
3VA1050-4ED42-0JA0