Breaking capacity reaches 121 kA at 240 VAC, 75.6 kA at 415 VAC, and holds at 11.9 kA at both 500 V and 690 VAC — that's the SCCR headroom for a 50 A frame in a distribution panel or motor control center.
The 50 A rating is continuous at 40–50 °C; above that the thermal derating curve drops it to 45 A at 70 °C. Power loss is 14.6 W maximum, which matters for enclosure heat rise calculations.
Integration Details
No communication function or undervoltage release on this variant.