Interrupting capacity and thermal derating
Interrupting capacity drops across voltage levels: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. Thermal derating starts at 55 °C: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, 56.7 A at 70 °C. In a sealed enclosure hitting 60 °C, you lose roughly 4 A of headroom — factor that into the load calc if the panel runs hot.