Siemens SENTRON 3VA1063-2ED32-0AE0 MCCB, 63 A, 3-Pole, 52.5

MPN3VA1063-2ED32-0AE0

Siemens SENTRON 3VA1063-2ED32-0AE0, molded case circuit breaker, 3-pole, 63 A, TM210 thermal-magnetic release, 52.5 kA at 240 V, 32 kA at 415 V, 4 HQ auxiliary switches, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1063-2ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1063-2ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1063-2ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-2ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-2ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1063-2ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-2ED32-0AE0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Its TM210 thermal-magnetic release gives fixed thermal pickup and magnetic trip settings, so you set the continuous current once and let the bimetal handle the overload curve. Rated continuous current Iu is 63 A, and it holds that rating all the way up to 50 °C ambient; above that it derates gradually, dropping to 56.7 A at 70 °C. Interrupting capacity is the real selector here: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

Panel fit and auxiliary contacts

The 3VA1063-2ED32-0AE0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that drops into most SENTRON distribution panels and switchgear assemblies without re-drilling. It ships with 4 HQ (high-performance) auxiliary switches built in, so you get status feedback for remote monitoring or PLC inputs without adding a separate contact block.

MCCBs of this class are the backbone of low-voltage distribution in industrial control panels, motor control centers, and building power distribution. The 63 A rating suits feeder circuits for groups of smaller motor starters, lighting panels, or sub-distribution boards.

Frequently asked questions

Where can I buy 3VA1063-2ED32-0AE0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ and we'll get you a firm price and lead time.

What is 3VA1063-2ED32-0AE0's interrupting capacity at 415 V?

At 415 V the interrupting capacity is 32 kA. That's the figure most panel builders will check for standard 400 V distribution boards — it means this breaker can clear a fault at that voltage without upstream current-limiting fuses.

Does 3VA1063-2ED32-0AE0 include auxiliary contacts?

Yes, it comes with 4 HQ (high-performance) auxiliary switches built in. That gives you status feedback for remote monitoring or PLC inputs without needing a separate add-on block.

What is the thermal derating of 3VA1063-2ED32-0AE0 above 50 °C?

It holds full 63 A up to 50 °C. Above that it derates: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If the breaker lives in a hot enclosure, use the derated figure for your load calculation.