Breaking capacity hits 52.5 kA at 240 V, drops to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The 70 mm depth, 76.2 mm width, and 130 mm height fit the standard SENTRON 3VA footprint, so it swaps into an existing panel layout without re-drilling the mounting holes or re-routing busbars.
The front IP40 rating means it's fine inside a clean enclosure but not for washdown areas — keep it behind a gland plate or cabinet door. Ambient temperature derating is straightforward: full 63 A from 40 °C up to 50 °C, then it steps down to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If the circuit needs remote trip or status feedback beyond the auxiliary switch, you'll add those as separate components. The TM210 release has a fixed time delay (tr max. 1 s) for the thermal curve; no field adjustment on the magnetic pickup.