Breaking capacity is 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V — figures that govern its fault-interrupting capability in different supply configurations.
Above that, derating is linear: 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. Maximum power loss is 17.3 W. Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm high — a standard 3-pole MCCB footprint that fits SENTRON panelboards and DIN-rail adapters without extra fillers.