Its 63 A rated continuous current (Iu) holds at ambient temperatures up to 50 °C without derating, then steps down to 60.48 A at 55 °C and 56.7 A at 70 °C — a thermal curve you can use directly for panel sizing.
Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.
Panel fit and auxiliary integration
The TM210 release is fixed-trip thermal-magnetic; no communication function or phase-failure detection on this variant. The integrated auxiliary trip order code is 3VA9608-0BB24 if you need a replacement spare.