Siemens 3VA1063-2ED42-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-2ED42-0DH0 SENTRON MCCB, 63A, 4-Pole, 52.5kA

MPN3VA1063-2ED42-0DH0

Siemens SENTRON 3VA1063-2ED42-0DH0, molded case circuit breaker, 4-pole, 63 A at 40 °C, breaking capacity 52.5 kA at 240 V, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1063-2ED42-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10632ED420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1063-2ED42-0DH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.19.8 W
3VA1063-2ED42-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1063-2ED42-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-2ED42-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1063-2ED42-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-2ED42-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens 3VA1063-2ED42-0DH0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, 4-pole, with a continuous current of 63 A at 40 °C and a rated insulation voltage of 800 V. That 63 A holds flat through 50 °C and only starts to taper at 55 °C — 62 A — dropping to 58 A at 70 °C, so you get full rating in most ventilated enclosures without derating. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V, which covers the high-fault end of most industrial distribution boards.

Dimensions are 130 mm high, 101.6 mm wide, 70 mm deep — a 4-pole MCCB that fits standard panel-mount cutouts for the SENTRON 3VA frame. The 70 mm depth leaves room behind the door for wiring and auxiliary wiring without crowding.

That means you get remote status (open/closed/tripped) and undervoltage protection without adding separate accessories. No ground-fault monitoring version on this variant. Maximum power loss is 19.8 W — plan for that in the enclosure thermal budget.

Frequently asked questions

How do I get current pricing and availability for 3VA1063-2ED42-0DH0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the breaking capacity of 3VA1063-2ED42-0DH0 at different voltages?

Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. That covers most industrial distribution fault levels up to the 690 V class.

Will 3VA1063-2ED42-0DH0 drop into a panel specified around 3VA1010-2ED32-0DC0 without rewiring?

Both are 4-pole SENTRON 3VA frame MCCBs with the same 130 mm height, 101.6 mm width, and 70 mm depth, so the mechanical footprint and bus-bar spacing are identical. The 3VA1063-2ED42-0DH0 is rated 63 A versus the 3VA1010's lower rating, so verify the upstream protection and cable sizing — but the panel cutout and mounting holes match.

What compliance documentation does Siemens provide for 3VA1063-2ED42-0DH0?

As a standard SENTRON MCCB, it carries CE marking for the European market and is designed to meet IEC 60947-2. UL and CSA listings are typical for the 3VA series, but confirm the specific certification for your jurisdiction at order time. RoHS and REACH declarations are available from Siemens documentation.

MPN