Line protection MCCB — 63 A, 3-pole, TM210 release
Interrupting capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that cover most industrial service-entrance and sub-distribution applications. The integrated auxiliary trip is order code 3VA9608-0BB11.
Thermal derating and ambient range
Above that it derates: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.
Undervoltage release and auxiliary switches are factory-installed — no field-assembly required for the listed configuration.