Skip to main content
Siemens 3VA1063-3ED32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-3ED32-0DA0 SENTRON MCCB, 63 A, 3-Pole, Line

MPN3VA1063-3ED32-0DA0

Siemens SENTRON 3VA1, molded case circuit breaker, 3VA1063-3ED32-0DA0, 63 A, 3-pole, TM210 overcurrent release, line protection, with undervoltage release, breaking capacity 75.6 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-3ED32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1063-3ED32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1063-3ED32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-3ED32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-3ED32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1063-3ED32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-3ED32-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A SENTRON MCCB with undervoltage release — line protection duty

The Siemens 3VA1063-3ED32-0DA0 is a SENTRON 3VA1 molded case circuit breaker (MCCB) rated for 63 A continuous current (Iu) at 40 °C, in a 3-pole configuration, designated for line protection. It carries a TM210 thermal-magnetic overcurrent release and an integrated undervoltage release (UVR) — the auxiliary trip order code for the UVR module is 3VA9608-0BB25. The rated insulation voltage is 800 V, and the front face is protected to IP40. Breaking capacity is specified at four voltage levels: 75.6 kA at 240 V AC, 52.5 kA at 415 V AC, 32 kA at 440 V AC, and 7.5 kA at 690 V AC. These figures govern the available fault current the breaker can safely interrupt at the point of installation — a key selectivity and SCCR coordination value for the panel designer. The TM210 release is a fixed thermal-magnetic type, not electronic, so no communication function or phase-failure detection is built in. The breaker has no auxiliary contact, no voltage trigger, and no ground-fault monitoring version fitted. It is a straightforward line-protection device for distribution panels where a simple thermal-magnetic curve and undervoltage protection are sufficient.

Thermal derating and operating range

The 63 A rating holds at ambient temperatures up to 50 °C. Above that, derating applies: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. The operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. For a panel builder, this means the breaker can be mounted in a warm enclosure without losing significant ampacity, as long as the ambient stays under 50 °C.

Mechanical integration and approvals

Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth — a standard 3-pole MCCB footprint for DIN-rail or panel-mount installation in distribution boards. The latching endurance is rated at 15,000 operations. The reference code per DIN EN 81346-2 is Q (switching device). The manufacturer's brand is SENTRON, part of the Siemens 3VA1 series.

Frequently asked questions

Where can I buy 3VA1063-3ED32-0DA0 and get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the breaking capacity of 3VA1063-3ED32-0DA0 at 415 V?

The breaking capacity is 52.5 kA at 415 V AC. At 240 V it is 75.6 kA, at 440 V it is 32 kA, and at 690 V it is 7.5 kA.

Does 3VA1063-3ED32-0DA0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as the auxiliary release type. The order code for the integrated auxiliary trip module is 3VA9608-0BB25.