Skip to main content
Siemens 3VA1063-3ED36-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-3ED36-0AD0 SENTRON MCCB, 63 A, 3-pole, Line

MPN3VA1063-3ED36-0AD0

Siemens SENTRON 3VA1063-3ED36-0AD0, molded case circuit breaker, 3-pole, 63 A, line protection, TM210 release, 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1063-3ED36-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1063-3ED36-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1063-3ED36-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-3ED36-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-3ED36-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1063-3ED36-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-3ED36-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

MCCB for line protection — 63 A, 3-pole, TM210 release

The interrupting ratings climb to 75.6 kA at 240 V and 52.5 kA at 415 V, so it clears high-fault currents without cascading upstream in a coordinated panel.

Above that it derates linearly: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.

Interrupting capacity by voltage

The 3VA1063-3ED36-0AD0 delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. In a 415 V distribution board with a prospective fault current of 50 kA, this breaker has headroom; at 690 V the 7.5 kA limit means it is suited only for low-fault installations or where upstream current-limiting devices reduce the let-through.

Auxiliary contacts and monitoring

This version ships with three auxiliary switches (HQ type) for remote status indication of the breaker's main contacts. The trip indicator is absent, so a blown breaker shows its state only through the auxiliary contacts or visual inspection of the handle. For a PLC input that needs a separate 'breaker tripped' signal, the three switches cover that; if you need undervoltage protection or ground-fault sensing, order a different 3VA variant.

The three auxiliary switches add wiring points on the side; plan for the extra terminal space in the wireway.

Frequently asked questions

Where can I buy 3VA1063-3ED36-0AD0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

What are the interrupting ratings of 3VA1063-3ED36-0AD0?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V.

Does 3VA1063-3ED36-0AD0 include an undervoltage release or ground fault monitoring?

No. There is no undervoltage release, no ground-fault monitoring, no shunt trip, no phase-failure detection, and no communication module.

MPN
3VA1063-3ED36-0AD0