It carries a continuous current rating of 63 A at 40 °C, with minimal thermal derating up to 70 °C (58 A at 70 °C), so the 63 A frame holds its rating across the typical panel ambient range without upsizing. This 3-pole breaker delivers interrupting ratings of 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that cover most industrial LV fault levels. At 500 V and 690 V the interrupting capacity drops to 7.5 kA, which still handles downstream fault contributions on 480 V or 600 V class systems when the available fault current is known to be below that threshold.

Siemens 3VA1063-3ED36-0JC0 SENTRON MCCB, 63 A, 3-Pole, 75.6
MPN3VA1063-3ED36-0JC0
Siemens SENTRON 3VA1063-3ED36-0JC0, molded case circuit breaker, 3-pole, 63 A at 40 °C, interrupting rating 75.6 kA at 240 V, 70 mm depth, 76.2 mm width, 130 mm height.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA10633ED360AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 63 A |
| Current at 45 °C | 63 A |
| Current at 50 °C | 63 A |
| Current at 55 °C | 62 A |
| Current at 60 °C | 61 A |
| Current at 65 °C | 60 A |
| Current at 70 °C | 58 A |
| Switching capacity class | N |
| Breaking capacity at 240 V | 75.6 kA |
| Breaking capacity at 415 V | 52.5 kA |
| Breaking capacity at 440 V | 32 kA |
| Breaking capacity at 500 V | 7.5 kA |
| Breaking capacity at 690 V | 7.5 kA |
| Power loss, max. | 17.3 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | box terminal on both sides |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
MPN