Skip to main content
Siemens 3VA1063-3ED36-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-3ED36-0KA0 SENTRON MCCB, 63 A, 3-Pole, 75.6

MPN3VA1063-3ED36-0KA0

Siemens SENTRON 3VA1063-3ED36-0KA0, molded case circuit breaker, 63 A, 3-pole, TM210 thermal-magnetic release, 75.6 kA interrupting at 240 V, IP40 front, shunt trip STL.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-3ED36-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1063-3ED36-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1063-3ED36-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-3ED36-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-3ED36-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1063-3ED36-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-3ED36-0KA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A MCCB with TM210 release — line protection for distribution panels

The Siemens SENTRON 3VA1063-3ED36-0KA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current (Iu) at 40 °C, with a TM210 thermal-magnetic overcurrent release. It holds its full 63 A rating through 50 °C ambient, then derates to 60.48 A at 55 °C and 56.7 A at 70 °C — a thermal curve worth checking if the breaker sits near other heat sources in a dense panel. Interrupting capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V, with a 7.5 kA floor at 690 V. That spread covers most low-voltage distribution fault levels in North American and IEC installations without needing a current-limiting upstream device. Rated insulation voltage is 800 V, and the front face carries IP40 protection — fine for a clean indoor panel, but not for washdown or outdoor exposure. The breaker includes a shunt trip (STL) auxiliary release (order code 3VA9688-0BL33 for the integrated trip unit), but no undervoltage release, no auxiliary contacts, no communication module, and no ground-fault monitoring. It is a straightforward line-protection MCCB — no frills, no firmware.

Panel fit and mounting dimensions

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mount panel layouts. Verify the bus-bar takeoff spacing if replacing an older frame; the 76.2 mm width matches the 3VA family pitch, so a panel wired for a 3VA1010 frame accepts this unit without re-drilling the gland plate.

Frequently asked questions

How do I get current pricing and availability for 3VA1063-3ED36-0KA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

Will 3VA1063-3ED36-0KA0 drop into a panel that was specified around 3VA1010-2ED32-0JA0 without rewiring?

The 76.2 mm width and 130 mm height match the 3VA1010 frame footprint, so the breaker fits the same mounting hole pattern and bus-bar spacing. The 63 A rating and TM210 release are a different trip curve from the 3VA1010's typical 10 A–32 A range, so verify the conductor sizing and upstream coordination — the mechanical fit is fine, but the electrical rating may require a coordination study.

What compliance documentation does this brand provide for 3VA1063-3ED36-0KA0?

As a Siemens SENTRON MCCB, this part carries the manufacturer's standard compliance documentation including CE marking, RoHS and REACH declarations, and IEC/EN 60947-2 certification. Specific UL listing status should be confirmed from the Siemens declaration of conformity for the exact order code.

MPN
3VA1063-3ED36-0KA0